PERFORMANCE OF A SINGLE STAGE VAPOUR COMPRESSION REFRIGERATION CYCLE AT LOW EVAPORATION TEMPERATURES

Authors

  • S. B. ADEYEMO Department of Mechanical Engineering, The Federal Polytechnic, Ado - Ekiti, Nigeria. Author

Abstract

At relatively high evaporating temperature, the single stage vapour compression cycle is an efficient method of refrigeration. As the evaporating temperature is reduced, the volumetric efficiency decreases, the coefficient of performance decreases and the power input per KW of refrigeration increases as well as the compressor discharge temperature.

The principal demerits of single stage refrigeration cycle operating at low evaporating temperatures are low refrigerating efficiency, low compressor volumetric efficiency (for reciprocating compressors) and a high compressor discharge temperature.

Decrease of compressor volumetric efficiency imposes a practical limitation on the single stage cycle and makes staging of the compressors necessary at low evaporating temperatures.

Using a multistage vapour compression cycle with intercooling of liquid and vapour refrigerant largely over-comes the disadvantages of the single stage cycle.

Downloads

Published

1992-06-30