ANALYSIS OF THE REACTIVE POWER FLOW AND VOLTAGE PROFILE IN THE NIGERIAN NATIONAL 330KV GRID

Authors

  • J. C. EKEH Department of Electrical & Electronics Engineering, Edo State University, Ekpoma, Nigeria. Author
  • P. A. KUALE Department of Electrical & Electronics Engineering, University of Benin, Nigeria. Author

Abstract

The reactive power flow in the Nigerian National 330KV Grid is reported in this paper. A FORTRAN computer program employing the Gauss-Seidel iterative technique is developed and used to evaluate the load flow of the national grid with a total of eighteen busbar case studies. It is found that the Shiroro-Kaduna 330KV transmission lines were overloaded and consequently exhibits unsatisfactory receiving end voltages at Kaduna, Kano, Jos, and Gombe 330KV loadbuses.

As a result of the study a reallocation of the reactive power sources in the Nigerian National 330KV Grid is suggested. This suggestion included the provision of shunt capacitors banks of values up to 97.50Mvar at Kano, 99.60Mvar at Gombe and 70.00Mvar reactor bank at Ajaokuta.